Manufactured by
Authorized Partner
Digital temperature controller / meter from the E5EC-800 series in a 1/8 DIN vertical (48 × 96 mm) size.
This model supports 24 Vac / 24 Vdc supply, 2 auxiliary outputs, 4 dry contact event inputs, and 1-channel heater burnout detection.
It features a large 3-row white backlit LCD, screw terminal connections, flush panel mounting, and IP66 front protection, making it suitable for demanding industrial temperature control applications.
Main function: Temperature controller (Digital)
Product series / family name: E5EC-800 series
Functions:
Digital temperature controller / meter
ON/OFF control or 2-PID control with auto-tuning
Manual output
Heating / cooling control
Loop burnout alarm
SP ramp
Other alarm functions
Heater burnout (HB) alarm (including SSR failure (HS) alarm)
40% AT
100% AT
MV limiter
Input digital filter
Self-tuning
PV input shift
Run / stop
Protection functions
Temperature status display
Moving average of input value
FB moving average
Design:
2 auxiliary outputs
4 dry contact event inputs
1-channel heater burnout detection
24 Vac / dc supply version
Supply voltage (AC): 24 Vac (50/60 Hz)
Supply voltage (DC): 24 Vdc
Frequency: 50 ms sampling period (20 Hz)
Display:
3 rows × 4-digits (negative transmissive 11-segment LCD with backlight)
18 mm digits height (PV; Present value; white backlight)
11 mm digits height (SV; Setpoint; white backlight)
7.8 mm digits height (MV; Multi-setpoint; white backlight)
Connection type: Screw connections
Mounting mode: Flush mounting on door
Digital inputs:
4 × digital inputs (dry contact) (event inputs)
Digital outputs:
1 × digital output (SPST-NO relay contact; 250 Vac / 5 A resistive load) (control output 1)
1 × digital output (SPST-NO relay contact; 250 Vac / 5 A resistive load) (control output 2)
2 × digital outputs (SPST-NO relay contacts; 250 Vac / 3 A resistive load) (aux. outputs)
Analog inputs:
1 × analog input (Main process input)
Thermocouple types K, J, T, E, L, U, N, R, S, B, W, or PL II
RTD Pt100, JPt100
IR temperature sensor
4–20 mA, 0–20 mA
1–5 Vdc, 0–5 Vdc, 0–10 Vdc
1 × analog input (Heater 50 A AC C.T. input) (Heater Burnout detection)
Measurement accuracy:
±0.3% of indication value or ±1 °C whichever is greater (thermocouple input)
±0.2% of indication value or ±0.8 °C whichever is greater (Platinum RTD input)
±0.2% F.S. ±1 digit max. analog input
±5% F.S. ±1 digit max. CT input (Heater Burnout detection)
±5% F.S. ±1 digit max. potentiometer input
Degree of protection: IP66
Dimensions: 1/8 DIN vertical (48 × 96 mm)
Net height: 96 mm
Net width: 48 mm
Net depth: 64 mm
Door cut-out height: 91 mm
Door cut-out width: 44 mm
Embedding depth: 60 mm
Ambient air temperature for operation: -10…+55 °C
Ambient air temperature for storage: -25…+65 °C
EAN code: 4548583318694
Compliant with standard(s):
UL61010-1
Korean Radio Waves Act (Act 10564)
CSA C22.2 No. 61010-1
IEC61010-1
EN61326-1
EN55011 Group 1 Class A
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-11
ICC
CE marking
Lloyd standards
Location of origin: China
Degree of pollution: 2
Benefits:
Large white PV display for improved readability
High-speed 50 ms sampling for fast response
Compact 60 mm body depth for space-saving panel installation
Easy PLC connectivity using programless communications